Basic Info | |
Model No. | CSI-7K/9K-S22003-E |
Output Power | >1000W |
Grid Type | Grid Inverter |
Output Type | Single |
Circuit Topologies | Push-Pull Type |
Nature Of Wave String | Sine Wave Inverter |
Type | DC/AC Inverters |
Transport Package | Catons And Pallet |
Specification | 7KW-9KW |
Trademark | CanadianSolar |
Origin | Nanjing, Jinagsu, China |
Production Capacity | 5000set/Year |
System Technical Data | ||
Model Name | CSI-7K-S22003-E | CSI-9K-S22003-E |
DC Input | ||
Max. DC Input Voltage (V) | 600 | |
Start-up DC Input Voltage (V) | 110 | |
MPPT Operating Voltage Range (V) | 100-500 | |
Rated Input Voltage (V) | 360 | |
Max. Input Current (A) | 15/30 | |
Max. Short-Circuit Current (A) | 18.8/37.6 | |
Number of MPP Trackers | 2 | |
Number of DC Inputs | 1/2 | |
AC Output | ||
Rated Output Power (W) | 7000 | 9000 |
Max. Output Power (W) | 7000 | 9000 |
AC Grid Connection Type | L/N/PE | |
AC Nominal Voltage And Range (V) | 220/230/240 (180-280) | |
AC Nominal Frequency And Range (Hz) | 50/60 (+5) | |
Max. Output Current (A) | 31.8 40.9 |
|
Displacement Power Factor | 0.8 leading to 0.8 lagging | |
Total Harmonic Distortion (THDI) | <3% | |
Efficiency | ||
Max. Efficiency | 98.1% | |
European Efficiency | 97.5% | |
Safety & Protection | ||
DC Switch | Integrated | |
Anti-Islanding Protection | Integrated | |
DC Reverse-Polarity Protection | Integrated | |
Insulation Monitoring | Integrated | |
Residual Current Protection | Integrated | |
AC Short-Circuit Protection | Integrated | |
AC Over Current Protection | Integrated | |
AC Over Voltage Protection | Integrated | |
Overvoltage Class | II (DC), III (AC) | |
General Parameters | ||
Dimensions (WxHxD, mm) | 399 x 446 x 192 | |
Net Weight (kg) | 19.5 | |
Installation Method | Wall-mounted | |
DC Connection Type | MC4, T6 | |
AC Connection Type | Connector | |
Communication | RS485/WiFi | |
Display | LED & APP | |
Cooling | Natural Convection | |
Protection Degree | IP65 | |
Operating Ambient Temperature Range (°C) | -25-60°C (>45°C, derating operation) | |
Relative Humidity (Non-Condensing) | 0% – 100% | |
Max. Operating Altitude (m) | 4000 m (>3000 m, derating operation) | |
Topology | Transformerless | |
Night Power Consumption (W) | <1 | |
Safety and EMC | IEC 62109-1/2, IEC 61000-6-1, IEC 61000-6-3 | |
Grid Connection Standard | ABNT NBR 16149/16150:2013, IEC61727 & IEC62116, AS4777 |